Annicom Axio Logo  
    +44(0)1420487788  
 
home | about us | products | datasheets | account
 
   
datasheetdetails
 <<  |  <  |   AX-ARL - Analogue to Raise Lower Module
AX-ARL / Analogue to Raise Lower Control Modules POA Qty
 <<  |  <  | OVERVIEW | SPECIFICATION | DATASHEETS        

The AX-ARL range converts a 0-10V dc input signal into a raise lower relay output pair. The modules can be configured, using jumpers, for two variable and one fixed range per unit. Applications include the control of window actuators or raise lower actuators, in conjunction with a BMS or standalone proportional controller. The AX-ARL is powered from 24Vac or 24Vdc, and is designed to fit onto TS35 Section DIN Rail.
Product Features
• 0-10Vdc Input
• 2 x SPCO Relay Output
• On/Off/Auto Override
• Two variable and one fixed range per varient
• Fixed and adjuatable time ranges
• LED indecation
• 24 Hour reset
• DIN rail mounting (TS35)

Input Signal
0-10V dc (1mA max)
Output Contacts
2 x SPCO
Contact Rating
12A at 250V ac (res.)
Power Supply
24Vac or dc
Power Consumption
70mA max at 24Vac
50mA max at 24Vdc

Modes of Operation, ARL Cycle times
90 to 300 secs/ 30 to 150 secs/ 210 secs
Modes of Operation, ARL2 Cycle times
10 to 30 secs/ 60 to 120 secs/ 90 secs
Manual Override
ON/OFF/AUTO (Link Selectable)
Reset
Automatic 24 hour reset for 115% of range
Terminals
Rising Clamp for 0.5-2.5mm² Cable
LED Indicators
ON when relay energised
Ambient Range
0 to 50°C
Dimensions
83mm (l) x 46mm (w) x 45mm (h) (approx.)
Weight
72 g
Country of Origin
United Kingdom

AX-ARL.pdf / Analogue to Raise Lower Control Modules