datasheetdetails
|
<< | < | AX-ARL - Analogue to Raise Lower Module
|
|
The AX-ARL range converts a 0-10V dc input signal into a raise lower relay output pair. The modules can be configured, using jumpers, for two variable and one fixed range per unit. Applications include the control of window actuators or raise lower actuators, in conjunction with a BMS or standalone proportional controller. The AX-ARL is powered from 24Vac or 24Vdc, and is designed to fit onto TS35 Section DIN Rail. |
Product Features
| • 0-10Vdc Input • 2 x SPCO Relay Output • On/Off/Auto Override • Two variable and one fixed range per varient
| • Fixed and adjuatable time ranges • LED indecation • 24 Hour reset • DIN rail mounting (TS35)
|
Input Signal
| 0-10V dc (1mA max)
| Output Contacts
| 2 x SPCO
| Contact Rating
| 12A at 250V ac (res.)
| Power Supply
| 24Vac or dc
| Power Consumption
| 70mA max at 24Vac
| 50mA max at 24Vdc
|
| Modes of Operation, ARL Cycle times
| 90 to 300 secs/ 30 to 150 secs/ 210 secs
| Modes of Operation, ARL2 Cycle times
| 10 to 30 secs/ 60 to 120 secs/ 90 secs
| Manual Override
| ON/OFF/AUTO (Link Selectable)
| Reset
| Automatic 24 hour reset for 115% of range
| Terminals
| Rising Clamp for 0.5-2.5mm² Cable
| LED Indicators
| ON when relay energised
| Ambient Range
| 0 to 50°C
| Dimensions
| 83mm (l) x 46mm (w) x 45mm (h) (approx.)
| Weight
| 72 g
| Country of Origin
| United Kingdom
|
AX-ARL.pdf / Analogue to Raise Lower Control Modules | |
|
|
|