The AX-CTX Voltage Output Analog Current Transmitters are designed for use in any AC current monitoring application in which you are looking to monitor a particular piece of equipment for proper operation. It uses an “Average”current measuring method and should be used in applications where a pure Sinusoidal AC waveform that has very little or no distortion/noise on the conductor being monitored. Applications may include monitoring a resistive type load such as an incandescent light bulb or heating element as well as any single-speed linear load. |
Product Features
| No external supply voltage required (for voltage output version) Cost-effective
| Multiple selectable ranges
|
Monitored current type
| AC
| Maximum AC voltage
| 600Vac
| Operating frequency
| 10 to 200 Hz
| Core style
| Solid core/ Split core
| Supply voltage
| Induced from monitored conductor (Voltage output versions)
| 24VDC±10% for Loop powered 4-20mA output versions
|
| Sensor Amperage Range
| Field selectable. (see order codes)
| Output signal
| 0-10VDC (Min 10KOhm load)
| Response time
| <200ms
| Accuracy
| +/- 10% from 5-100% of selected range
| Electrical connections
| 2 way screw terminal block (Polarity Sensitive)
| Aperture size
| 20.00mm
| Ambient temperature/humidity
| 0°C to 50°C / 10-95% RH non-condensing
| Enclosure material
| ABS
| Flammability rating
| UL94-V0
| Dimensions/Weight
| 61.5×90×26mm for Solid core
| 63×100×32.2mm for Split core
|
| Country of origin
| United Kingdom
|
AX-CTX.pdf / AC Current Transmitter-Voltage Output | |
|
|
|