datasheetdetails
|
<< | < | AX-GLD-P82 - Gas Leak Detection System - 4 Zone
|
|
The AX-GLD-P82 Gas Leak Detection system is suitable for use in Boiler Rooms and other Commercial applications to provide safety and shut down facilities in the event of gas leakage. The Control unit has upto 4 zones for connecting upto 4 remote sensors. They are mounted in DIN rail housings The units come complete with output relays to operate auxiliary devices such as Gas Solenoid Valves or sirens and fault remote signalling are fitted to all units. |
Product Features
| • 12Vac/dc supply • Upto Four Zones • Audio and Visual Alarm
| • Adjustable Alarm Sensitivity • Relay output for Gas Valves and Remote Alarms • Auto or Manual Reset
|
Power Supply
| 12Vac/dc +/- 10%
| Power Consumption
| 1 sensor 160mA ( max 320mA)
|
| 4 sensors 280mA (max 920mA)
| Relay Contact Rating
| 2 x SPDT 8(1)A@250Vac
| Alarm Thresholds
| well below the Gas LEL 16%
| Audible Alarm
| Approx 60db @1m
| Ambient Temp. Range
| -10 deg C to + 50degC
| LED Indication
| Control Unit Red Power on
|
| Yellow General Failure
|
| Yellow 4 x sensor fault
|
| Red 4 x gas alarm
| Maximum Distance Control to Sensor
| 50m
| Dimensions
| 158 x 90 x 58mm (9 DIN)
| Weight
| Control Unit 0.25 kgs
|
| Sensors 0.18kgs
| Protection
| Control Unit IP40
|
| Sensor IP54
| Conformity
| CE marked,
|
| EN61779-1-4; CEI 216-5/1; EMC 89/336/CEE; EN 50270
| Country of Origin
| Italy
|
AX-GLD-P82.pdf / Gas Leak Detection System - 4 Zone |  |
|
|
|