datasheetdetails
|
<< | < | AX-GS-CD-T81 - Carbon Dioxide Sensor with Optional RH
|
|
The AX-GS-CD-T81 Combined Humidity, Temperature and Carbon Dioxide Transmitter uses NDIR single beam Infrared technology to monitor the CO2 levels and give both a Voltage and Current output of CO2 levels and a Thermistor to monitor the Temperature and a Thermoset Polymer Based Capacitive sensor for the RH and outputs a linear signal as either 4-20 mA or 0-5/10 Vdc. The options include a LCD display displaying the ppm levelsand Bacnet output |
Product Features
| • Wall mounting • Monitors CO2 over range 0 to 2,000 ppm • Optional Temperature and RH Outputs
| • Solid State Sensing Element • Lifetime calibration interval • Adjustable Analogue Output
|
Power Supply
| 18 to 30Vac 50/60Hz
| Consumption
| 0.7W @nominal voltage of 24Vac
| Ambient Temp. Range
| 0 to +50’C , 0-95% RH non condensing
| LCD Display
| (optional) Displays all parameters 33 x 14 mm (optional at additional cost)
| Housing
| Flame retardant ABS
| Dimensions
| 82 x 87 x 28 mm
| Analogue Outputs
| 0-10V (100 ohm output impedance)
|
| 4-20mA (RL maximum 500 ohm)
|
| Bacnet MSTP (optional extra)
| Conformity
| CE marked, EMC, LVD.
| Country of Origin
| Mexico
|
| Carbon Dioxide
| Sensor Type
| Non-dispersive Infra-red
| Range
| 0-2000ppm standard, 0-5000ppm available (-S version)
| Calibration Interval
| Lifetime
| Accuracy
| +/- 30ppm or 5% whichever is greater
| Stability
| Self Calibrating <2% FS over life of sensor (typical 15yrs)
| Altitude Correction
| Programmable from 0-5,000ft in 500 ft increments
| Output
| 0-5/10Vdc and 4-20mA
|
| -EB Bacnet MS/TP RS485 38400 or 9600 baud + Relay
| Settling Time
| <2 minutes after power up (10 minutes maximum accuracy)
|
| Temperature
| Sensor Type
| 10K3A1 Thermistor
| Temperature Range
| 0-50’C
| Temperature Accuracy
| +/- 1’C
| Output
| Thermistor or 0-5/10Vdc or 4-20mA
|
| Relative Humidity
| Sensor Type
| Thermoset Polymer Based Capacitive
| RH Range
| 0-99%RH (non-condensing)
| RH Accuracy
| +/- 2.5% RH (20-80%RH)
| Output
| 0-5/10Vdc or 4-20mA
|
AX-GS-CD-T81.pdf / Carbon Dioxide Sensor with Optional RH & T and Bacnet Outputs | |
|
|
|