datasheetdetails
|
<< | < | AX-GS-CM-NO2-M - Nitrogen Dioxide and Carbon Monoxide Transmitter, MODBUS RTU
|
|
The AX-GS-CM-NO2-M is an ideal solution for detecting harmful emissions in parking garages, loading docks, warehouses etc. It offers detection of carbon monoxide and nitrogen dioxide gases in the same enclosure . Sensor readings are transmitted over RS-485 Modbus RTU protocol. By monitoring the levels of CO and NO2 in the air, the ventilation system can be adjusted to ensure that the air quality is within safe limits. |
Product Features
| • Detection range - CO: 0 to 300 ppm ,NO2: 0 to 10ppm • Isolated RS485 output • Electrochemical sensing elements
| • Zero and sensitivity adjustments for field calibration • Easy installation with plug-in connections • UL listed sensors: File no. E240671
|
Power Supply
| 24Vac ±10%, 100mA maximum or 24Vdc ± 10%, 60mA maximum
| Sensor Type (CO and NO2)
| Electrochemical 3-electrode
| Output Range
| CO
| Output Accuracy
| CO
| Response time(t90)
| < 35 seconds
| Long term sensitivity drift
| CO
| Typical Coverage Area
| 700m² or 15m radius
| Settling Time
| 3 minutes after power up
| Life Expectancy
| NO2
| Ambient Temperature & Humidity
| 0-50°C, 15-90% RH non-condensing
| Housing
| Flame retardant ABS, IP65 White ( optional Black-see order codes)
| Dimensions & Weight
| 92mm diameter x 52mm, 180gms
| Terminals
| Rising clamp for 0.5-1.5mm² , 2 Part Pluggable
| Communication
|
| Protocol
| M odbus RTU protocol over RS485
| Address range
| 1-63 (settable using dipswitch), 1-247 (settable using configuration register)
| Baud rates supported
| 9600bps,19200bps,38400bps,57600bps,115200bps
| Parity
| None (default), Odd, Even (odd, even selectable via configuration register)
| Number of stop bits
| 1(default),2 (2 is selectable via configuration register)
| Isolation
| 1500VDC (60sec, <1mA leakage current) between Power and Output
| 120Ohms termination
| Available on board. Enabled using jumper
| Recommended cable
| 24AWG twisted pair shielded cable (1 pair for data and 1 conductor for common)
| Maximum devices on a network
| 32
| Warranty
| 5 years for the product. (NO2 sensor
| Country of origin
| UK
|
AX-GS-CM-NO2-M.pdf / CO 0-300ppm , NO2 0-10ppm transmitter, RS485 Modbus |  |
|
|
|