datasheetdetails
|
<< | < | AX-GS-TC30A-PHC - Flammable Gases Sensors - Wall Mount
|
|
The AX-GS-TC30A-PHC Transmitter uses catalytic pellistor sensor which is a cost effective version to detect all flammable gasses such as (propane, butane, propylene, butylene and isobutane) which is collectively called LPG. This unit has 3-wire 4-20mA and addressable outputs. |
Product Features
| • Wall Mounted • 4-20mA linear output • Optional Duct Sampling Kit
| • IP54 ABS housing • Pre-calibrated • For Safe area sensing
|
Sensor Type
| Catalytic pellistor
| Gas
| LPG
| Sensor Range
| 0-100% LEL
| Power Supply
| 18-28Vdc
| Typical Cell Life
| >3 years
| Accuracy
| ± 2 % FSD
| Stability
| <5% signal loss per year
| Output
| 3-wire 4-20mA &/or Addressable
| Housing
| IP54,ABS
| Ambient temp. range
| -5 to +50°C
| Ambient RH. range
| 5-95% RH non condensing
| Dimensions
| 148 x 88 x 47mm
| Weight
| 425 Grams
| Conformity
| CE, Declaration of conformity in accordance with EN ISO/IEC 17050-1
| EMC 2004/108/EC
|
| Low voltage 2014/35/EC
|
| Gas EN50271
| 2018
| Country of Origin
| United Kingdom
|
AX-GS-TC30A-PHC.pdf / Flammable Gases Sensors - Wall Mount | |
|
|
|