datasheetdetails
|
<< | < | AX-OC-MWS-3 - Microwave Occupancy Detector - Ceiling Corridor Mount
|
|
The AX-OC-MWS-3 programmable microwave occupancy detectors provide automatic control of lighting, heating or ventilation loads. The AX-OC-MWS-3 detects movement using a highly sensitive microwave detector. This works by emitting low power microwave signals and measuring the reflections as the signals bounce off moving objects. The AX-OC-MWS-3 has a unique adjustable sensor head that allows the area of detection to beoptimised for the application. When movement is detected the load is turned on. When an area is no longer occupied the load will switch off after an adjustable time out period. An internal light sensor provides additional energy savings. When an area is occupied lighting is only switched on when the level of natural light is below a preset level. An integral IR sensor in the unit allows the parameters to be changed and the sensor to be overridden using a remotecontrol handset . |
Product Features
| • Ceiling Mounting • Volt free contact output option
| • Microwave occupancy detector • Hand held programmer for fast commissioning
|
Sensor type
| Microwave and Light Level
| Field of View
| see data sheet
| Power Supply
| -3 - 220-240Vac 50Hz
|
| -3L - 12/24Vac/dc
| Output
| switched live or Volt Free contact options
| Load
| NO 10A,240Vac maximum resistive and incandescent lighting
|
| 6A 240Vac flourescent lighting
|
| 3A,240Vac low energy lighting, compact flourescent lighting and fans
| Delay Timer
| Adjustable 10 seconds to 99 minutes
| Programmable Parameters
| LUX level, Time Delay, Presence or Absence,
|
| Power up ON or delay (30secs)
| Electrical Connections
| 2.5mm²
| Ambient Temp. Range
| -10 to + 35°C
| Housing
| Flame retardant ABS, fixing clip polypropylene IP40
| Microwave Radiation
| Extremely low power complies with ANSI IEEE95.1-1999
| Microwave frequency
| 10.687GHz approved for use in UK, Middle East, China, India (alternative frequencies available for other countries)
| Conformity
| EMC 2004/108/EC, LVD 2006/95/EC
| Country of Origin
| United Kingdom
|
AX-OC-MWS-3.pdf / Microwave Occupancy Detector - Ceiling | |
|
|
|