<< | < | AX-OC-MWS-C1 - Microwave Occupancy Detectors - Ceiling Overhead Mount
|
|
The AX-OC-MWS-C1 microwave presence detectors provide automatic control of lighting, heating or ventilation loads. The units detect movement using a highly sensitive microwave detector. This works by emitting low power microwave signals and measuring thereflections as the signals bounce of moving objects. The AX-OC-MWS-C1 is for overhead ceiling mounting applications. When movement is detected the load is turned on. The unit has an internal light sensor which can provide additional energy saving in lighting applications . The unit is controlled and programmed using handheld IR Handsets |
Product Features
| • Ceiling overhead Mounting • Switched Live or Volt free contact output. • Microwave presence detector
| • Programmable via handheld programmer • Status LED
|
Sensor type
| Microwave and Light Level for overhead ceiling mounting
| Field of View
| See diagram
| Power Supply
| -1 and -1VF 220-240Vac 50Hz 1.15W maximum
|
| -1LVF 11.5 to 36Vdc or 10 to 26.5Vac 1.1W maximum
| Load
| NO 6A,240Vac maximum resistive, incandescent and flourescent lighting
|
| 3A,240Vac low energy lighting, compact flourescent lighting and fans
|
| -VFC NC 2A,240Vac maximum resistive
| Delay Timer
| Adjustable 10 seconds to 99 minutes
| Electrical Connections
| 2.5mm²
| Ambient Temp. Range
| -10 to + 35°C
| Materials
| Flame retardant ABS,
| Microwave Radiation
| Extremely low power complies with ANSI IEEE95.1-1999
| Microwave frequency
| 10.687GHz approved for use in UK, Middle East, China, India (alternative frequencies available for other countries)
| Conformity
| EMC 2004/108/EC, LVD 2006/95/EC
| Country of Origin
| United Kingdom
|