datasheetdetails
|
<< | < | AX-OCF - Occupancy Sensors
|
|
The AX-OCF range of occupancy sensors are passive infra-red sensors for monitoring occupation through body heat. Detection of occupation will activate the internal relay . There are switched live and Volt free output variants. The units include a light level control which can be turned off if required. There are 230Vac and 24Vac/dc variants |
Product Features
| • Flush, Surface and Wall mount options • Switched live orVolt free contact output options
| • Compatible with many BMS products • Adjustable timer
|
Sensor type
| Passive Infra-Red Detector
| Field of View
| Flush & Surface 360 degrees
|
| Wall 110 degrees
| Coverage
| Flush & Surface 8 metres diam max. (at 2.8m height)
|
| AX-OCF-230F6 12 metres diam. max (at 6m height)
|
| Wall upto 10 metres.
| Power Supply
| -24 24Vac/dc +/- 20% (flush and surface only)
|
| -240 96 to 253Vac 50/60Hz
| Output
| Switched Live Supply voltage
|
| Relay SPST- NO
| Contact Rating
| 10 A @240Vac resistive
| Timer
| 10 secs to 12 mins
| Light Level
| Adjustable threshold (if fitted)
| Ambient Temp. Range
| -10 to +50°C
| Materials
| Flame retardant ABS, polypropylene
| Conformity
| CE marked, EMC, LVD.
| Country of Origin
| Italy
|
AX-OCF-xx.pdf / Occupancy Sensors |  |
|
|
|