<< | < | AX-PM-DRK - Din Rail Mounted kWh Meter - Direct
|
|
TheAX-PM-DRK range of kWh meters are a compact DIN rail mounted design. There are both direct connected and CT connected versions for both single and three phase supply. The units give a pulse output to the BMS |
Product Features
| • Single and three Phase versions • Direct and CT operated versions
| • Pulse output to BMS • DINrail mounted
|
PowerSupply
| Single Phase 230Vac 50/60Hz Line to Neutral
|
| Three Phase 230Vac 50/60Hz Line to Neutral
|
| 400V Line to Line
| FrequencyRange
| 45 to 65Hz
| Maximum Current
| Direct connected
|
| Single Phase 63Amps
|
| Three Phase 90Amps
|
| CT connected 5Amps (max 6A)
| Minimum Start up Current
| <50mA (<15mAfor CToperated)
| Power Consumption
| Voltage Circuit Max<4VA(0.5W)
|
| Current Circuit Max<2VA
| Pulse Output
| 1 per 0.1kWh
| Pulse Duration
| <75ms Voltage 3-30VdcCurrent < 20mA
| CT Ratio’s
| CT connected only
| Precision Class
| Class 2 in accordancewith CEI-EN61036
| LED Indication
| Green- Power on Red-Metering energy 1 flash per pulse
| Protection
| IP20
| Dimensions
| 70(w) x87(h) x 65 (d)mm
| AmbientTemp.Range
| -10 to +45deg C, 0-95%RH
| Conformance
| 72/23/EECmodified by93/68/EEC LowVoltage
|
| 89/336/EECmodified by92/31/EECand 98/68/EEC
|
| Safety CEI-EN61010-1(1994)
|
| EMC CEI-EN61036(1997)
|
| Measurement Accuracy CEI-EN61036 (1997)
| Country ofOrigin
| UK
|