datasheetdetails
|
<< | < | AX-RH-T-CD - Combined RH, T and Co2 Transmitter
|
|
The RH-T-CD Combined Humidity, Temperature and Carbon Dioxide Transmitter uses NDIR single beam Infrared technology to monitor the CO2 levels a Thermistor to monitor the Temperature and a Thermoset Polymer Based Capacitive sensor for the RH and outputs a linear signal as either 4-20 mA or 0-5/10 Vdc. Operating parameters are easily programmed by an on-board keypad to configure the transmitter to a specific application. The optionsinclude a LCD display displaying the ppm levels and the option of Modbus or Bacnet output |
Product Features
| • Wall mounting • Fully menu driven set-up/ calibration • Monitors CO2 over range 0 to 2,000 ppm • Solid State Sensing Element
| • Optional Modbus or Bacnet output • 5 year calibration interval • Adjustable Analogue Output
|
Power Supply
| 20 to 30Vac/dc @80mA max
| Consumption
| 125mA @ 24V max (typical 75mA)
| Ambient Temp. Range
| 0 to +50’C , 0-95% RH non condensing
| LCD Display
| (optional) Displays all parameters 33 x 14 mm (optional at additioanl cost)
| Housing
| Flame retardant ABS
| Dimensions
| 119 x 71 x 32 mm (Bacnet variant in a different housing)
| Conformity
| CE marked, EMC, LVD.
| Country of Origin
| Canada
|
| Carbon Dioxide
| Sensor Type
| Non-dispersive Infra-red
| Range
| 0-2000ppm standard, programmeable from 1500 upto 20,000ppm in 500ppm steps
| Calibration Interval
| 5 years
| Accuracy
| +/- 50ppm or 3% whichever is greater
| Stability
| Self Calibrating <2% FS over life of sensor (typical 15yrs)
| Altitude Correction
| Programmable from 0-5,000ft in 500 ft increments
| Output
| 0-5/10Vdc or 4-20mA (Modbus or Bacnet output available at additional cost)
| Settling Time
| <2 minutes after power up
| Response Time
| <2 minutes for 90% step change
|
| Temperature
| Sensor Type
| 10K3A1 Thermistor
| Temperature Range
| 0-35 or 0-50’C - selectable
| Temperature Accuracy
| +/- 0.2’C
| Output
| 0-5/10Vdc or 4-20mA (Modbus or Bacnet output available at additional cost)
|
| Relative Humidity
| Sensor Type
| Thermoset Polymer Based Capacitive
| RH Range
| 0-100%RH
| RH Accuracy
| +/- 2% RH
| Output
| 0-5/10Vdc or 4-20mA (Modbus or Bacnet output available at additional cost)
| RH Response Time
| 15 seconds typical
| RH Stability
| +/- 1%RH typical @50% RH in 5 years
|
AX-RH-T-CD.pdf / Combined RH, T and Co2 Transmitter |  |
|
|
|