The Axio AX-RLA isolates and converts a raise-lower input signal into a 0-10 volt analogue output. The unit provides sixteen raise-lower cycle times and a manual output override for commissioning. The input common can be connected to the signal 0V or supply voltage allowing the inputs to be voltages (AC/DC) or switching signals. Input load resistors can be selected for triac switching. The unit also provides a 24V supply feed through for valve actuators, etc. to simplify cabling. The AX-RLA is supplied in a DIN rail carrier suitable for mounting on TS35 section DIN rail and features high quality rising clamp terminals for ease of connection.
Product Features
• Isolated Raise Lower inputs
• 12 to 24 Vac/dc or volt free inputs
• Raise and lower input LEDs
• 24Vac/dc powered
• Sixteen cycle time options
• Built in triac load resistors
• Override preset for commissioning
• DIN rail carrier (TS35 DIN rail)

Supply voltage
24Vac or 24Vdc (+/-15%)
Supply current
30 mA DC / 60 mA AC (Not including input current)
Inputs
12 to 24 Vac/dc or volt free Raise and Lower signals
Input load
Approximately 10mA at 24Vac with J1 or J2 in N position

Approximately 50mA at 24Vac with J1 or J2 in T position
Raise Lower timing
30 to 300 seconds, see table
Outputs
0 - 10Vdc at 10mA maximum load
24V supply feed through
Terminals
Ambient temperature range
0°C to 50°C
Dimensions
45(W) x 83(H) x 45(D) mm (Maximum)
Weight
50 grams