datasheetdetails
|
<< | < | AX-RLA-24-ACT - Raise Lower to Analogue Convertor-24Vac
|
|
The Axio AX-RLA-24-ACT converts 24Vac raise-lower input signals into a 0-10 volt analogue output. The unit provides various cycle times that are jumper selectable. The AX-RLA-24-ACT is powered from 230Vac and provides a 24Vac supply for valve actuators, etc. to simplify cabling. The unit features a manual preset for commissioning purposes. The module is supplied in a DIN rail carrier suitable for mounting on TS35 section DIN rail and features high quality rising clamp terminals for ease of connection. |
Product Features
| • 24Vac Raise Lower Inputs • 24Vac output at 2.5VA • Manual override preset for commissioning
| • Selectable cycle times • 230Vac powered • DIN rail carrier (TS35 DIN rail)
|
Supply voltage
| 230Vac (+/-15%), 50-60Hz
| Inputs (Raise and Lower)
| 24Vac (+/-15%), 50-60Hz
| Input load
| 10mA normally with J1 or J2 in position N
| 60mA normally with J1 or J2 in position T
|
| Raise-Lower timing
| 30 to 300 Seconds – see table 1
| Analogue output
| 0 - 10Vdc at 5mA maximum load
| Power output
| 24Vac at 2.5VA maximum. Typical regulation 25%
| Fuse
| Transformer output protection - 250mA anti-surge
| Terminals
| Rising clamp for 0.5-2.5mm² cable
| Ambient temperature range
| 0°C to 50°C
| Dimensions
| 68(W) x 83(H) x 58(D) mm (Maximum)
| Weight
| 250 grams
| Country of origin
| United Kingdom
|
AX-RLA-24-ACT.pdf / Raise-Lower to Analogue converter | |
|
|
|