datasheetdetails
|
<< | < | AX-WLD-DT-M - Drip Tray Monitor - Modbus RTU
|
|
The AX-WLD-DT-M is a water level alarm module. It is intended for monitoring the condensate levels in drip trays on air-conditioning units. The unit comprises two stainless steel probes and integrated electronics to transmit the signal over Modbus RTU. The probes are mounted at the level required to generate an alarm signal. The excitation signal generated by the unit for the sensor connections ensures that the probes do not degrade when exposed to damp for long periods. |
Product Features
| • 24V ac/dc operated • Isolated RS-485 output
| • Internal excitation of probes ensures long probe life • IP65 Enclosure
|
Supply voltage
| 24Vac @ 50Hz ±10% or 24Vdc ±10% at 50mA max
| Power consumption
| 1.5W max
| Excitation
| AC, Internal
| Probe material
| Stainless steel 303
| Communication Protocol
| Standard Modbus RTU protocol over RS485
| Address range
| 1-63 (settable using dipswitch), 1-247 (settable using configuration register)
| Baud rates supported
| 9600bps,19200bps,38400bps,57600bps
| Parity
| None (default), Odd, Even (odd, even selectable via configuration register)
| Number of stop bits
| 1(default),2 (2 is selectable via configuration register)
| Isolation
| 1500VDC between Power and Output
| 120Ohms termination
| Available on board. Enabled using jumper
| Terminals
| Rising clamp 0.5-1.5mm² cable
| Ambient Temperature Range
| -10°C to 50°C
| Ambient Relative humidity
| 0-90% Non condensing
| Enclosure material
| ABS
| Dimensions
| 104 x 104 mm
| Weight
| 100gm
| Ingress protection
| IP 65
| Country of origin
| United Kingdom
|
AX-WLD-DT-M.pdf / Drip Tray Monitor - Modbus RTU |  |
|
|
|