datasheetdetails
|
<< | < | E925 - Standard Humidistat
|
|
The E925 will accurately control the humidity of an area to a fully adjustable relative humidity setpoint between 5% and 95%, combined with an adjustable relative humidity hysteresis (differential) of anything between 1% and 10%. The unit is supplied as a wall mounted unit that is designed to fit into a British Standard electrical back box. |
Product Features
| The E925 offers a calibration-free, high quality contemporary solution to humidity control. Utilising a high accuracy humidity sensor the E925 regulates to a fully adjustable relative humidity set-point between 5% and 95%, combined with an adjustable relative humidity hysteresis (differential) of anything between 1% and 10%. Loads of up to 10A such as ventilation, extraction, humidification and dehumidification equipment can be controlled by the humidistat via its volt-free relay output. The E925 is supplied as a wall mounted unit that is designed to fit into a British Standard electrical back box.
| Humidistat Variants: 24 Volt (/24V) Powered by 24 volt (AC or DC) supply. *For a full description please see relevant variation below.
|
Power supply
| 220V - 240V AC 50Hz (live/neutral)
| ā/24Vā variant
| 22V - 26V AC or DC
| Output switch rating
| 10A, 250V AC 50Hz (resistive)
| Output switch type
| Changeover relay (volt-free)
| Humidity control
| 5% RH to 95% RH
| Humidity differential
| 1% RH to 10% RH
| Sensor accuracy
| +/- 3% RH
| Sensor drift
| +/- 1.2% RH over 5 years (no calibration required)
| Guarantee
| 5 Years
| Weight
| 97g
| Dimensions
| 86mm x 86mm x 26.9mm
| Country Of Origin
| UK
|
E925-StandardHumidistat.pdf / Standard Humidistat + LED Indicators | |
|
|
|